The Majestic Lanai and the Majestic Courtyard are both outdoor-listed gas fireplaces, and both follow the same rules for screened and covered spaces. They differ in how they're built in. The Lanai is a linear unit (48" or 60") that goes into a framed enclosure. The Courtyard is a traditional firebox (36" or 42") that can stand alone or be built into a wall. Pick the Lanai for a long, low flame, and the Lanai 60 for the most heat (65,000 BTU); the Lanai 48 and the Courtyard are both 55,000 BTU on natural gas. Pick the Courtyard if you want a traditional firebox with brick-pattern refractory panels, a lighter unit and less building work. Every figure below comes from Majestic's installation and owner's manuals.
The short answer
- Heat: the Lanai 60 is rated 65,000 BTU and the Lanai 48 55,000 BTU, the same on natural gas and propane. Both Courtyard sizes are rated 55,000 BTU on natural gas and 53,000 on propane.
- Screened lanais and covered patios: both units use the same rule. With a roof and three walls, at least 30% of the perimeter must stay permanently open. 14x18 or 16x18 mesh is approved. Solar screen and no-see-um screen are not.
- Building work: the Lanai needs a framed enclosure with a 1/2" air space at the back and sides and noncombustible sheathing above. The Courtyard shows 0" to the back and sides and can be installed as a stand-alone unit.
- Finish: the Courtyard models we sell (-NR) must be finished with a refractory liner kit, sold separately. The Lanai takes a driftwood log set or a stone kit.
- Power and gas: both need a GFCI-protected 110–120V circuit, and both convert to propane with a kit.
Side by side, from the manuals
Sources: Majestic's Lanai installation manual (ODLANAIG-48/60, 4111-901 Rev. J), the Lanai owner's manual (4111-900 Rev. M), Majestic's Courtyard installation manual (ODCOUG-36/42, 4150-901 Rev. F) and the Courtyard owner's manual (4150-900 Rev. I). A dash means the manual doesn't state the figure in a form we could confirm.
| Lanai 48 / 60 (ODLANAIG) | Courtyard 36 / 42 (ODCOUG) | |
|---|---|---|
| Style | Linear burner | Traditional firebox |
| Max input, natural gas | 55,000 / 65,000 BTU | 55,000 BTU (both sizes) |
| Max input, propane | 55,000 / 65,000 BTU | 53,000 BTU (both sizes) |
| Viewing area | 47-7/8" x 17" / 60" x 17" | — |
| Framing (width x height x depth) | 52-3/4" x 39-3/4" x 13-3/8" / 64-3/4" x 39-3/4" x 13-3/8" | — |
| Weight | 215 / 245 lb | 90 / 95 lb (-NR) |
| How it's installed | Built into a framed enclosure; noncombustible sheathing above; cement board supplied for minimum-height installs | Stand-alone or built into a wall |
| Back and sides | 1/2" air space at back and sides | 0" to back, 0" to side |
| Clear space in front | Both: 36" (3 ft) to furniture and other combustible objects | |
| Ceiling | 39" minimum, measured from the top of the firebox opening | 36" minimum, measured from the top of the appliance opening |
| Overhang and soffit | 39" below a ventilated or unventilated soffit; 60" below vinyl soffit; 72" below a vinyl or composite overhang | 36" below a ventilated or unventilated soffit and under a veranda, porch, deck or balcony; 60" below vinyl soffit or electrical service; 72" below a vinyl or composite overhang |
| Enclosure rule | Same for both. Outdoors means walls on all sides with no roof, a roof with no more than two side walls, or a roof with three side walls if at least 30% of the perimeter is permanently open. 14x18 and 16x18 screen mesh approved; "DO NOT use solar screen or no-see-um screen." | |
| Propane conversion | LPK-ODLANAIG48 / LPK-ODLANAIG60 | ODCOUG-LPK (both sizes) |
| Drainage | Drain holes in the base; builder must provide a drain path; drain pan sloped 1/4" per foot toward the drain ports; optional ODLANAIG-48DP / -60DP drain pans | Drain holes in the base; builder must provide a way to drain the enclosure; 1/4" per foot toward the drain ports; optional ODGSDP-36 / -42 and flat ODGSDPFLT-36 / -42 drain pans |
| Electrical | 110–120 VAC, 60 Hz, under 12 A; GFCI-protected and unswitched | 110–120 VAC, 60 Hz, under 3 A; GFCI-protected, unswitched to the junction box |
| Ignition | IntelliFire intermittent pilot ignition (IPI), wall control | IntelliFire intermittent pilot ignition (IPI), wall switch |
| Listing | Both: ANSI Z21.97-2017 / CSA 2.41-2017, outdoor decorative gas appliance | |
| Altitude (USA) | Both: reduce input 4% for each 1,000 ft above 2,000 ft | |
| Media and accessories | CDLS driftwood log set or STONEKIT (not together); 48SCN / 60SCN screens; 48CFT / 60CFT clean face trim | Refractory kit required on -NR models (36" / 42" liner panels); optional SDLOGS-ODCOUG or HDLOGS-ODCOUG log sets with GR-ODCOUG grate; lava rock; ODCOUG-36SCN / -42SCN framed mesh screens |
| Warranty | Both: Outdoor Lifestyles Limited Warranty. Limited lifetime on the body, metal firebox and heat exchanger; one year on gas and electrical components, glass, accessories and labor. | |
A screened Florida lanai
The enclosure rule doesn't separate the two. Both manuals use the same 30%-open test and the same mesh rule, so the question is whether your lanai passes, not which fireplace you choose. If your cage has no-see-um or solar screen on its open sides, neither unit is allowed there. Majestic's manuals allow approved screen on the open sides but don't say whether a screened side counts toward the 30%; before you rely on a screened side, confirm with Majestic (through us) and your local building department. Our screened lanai and pool cage guide works through the 30% sum for a typical cage.
The overhead figures are close. Both need 60" below vinyl soffit and 72" below a vinyl or composite overhang. On a plain ceiling the Courtyard needs 36" and the Lanai 39", both measured from the top of the appliance opening.
The bigger difference is the building work. Adding a fireplace to an existing lanai is usually a retrofit, and the Courtyard's 0" back and side clearances and stand-alone option mean it doesn't need a framed chase. The Lanai needs a framed enclosure with a 1/2" air gap and noncombustible sheathing above. That makes it a better fit for a lanai that's being built or remodeled, when the wall is being framed anyway. On a flat slab, either unit needs a drain path: Majestic says the builder must provide a way for water to leave the enclosure.
An open desert patio
A patio with no roof is outdoors under both manuals, so the ceiling, soffit and 30% rules don't apply. What's left is heat and installation. The Lanai 60's 65,000 BTU is the highest rating here, and the Lanai keeps its full rating on propane. The Courtyard drops from 55,000 to 53,000 BTU on propane, which matters if your patio runs off a tank. Above 2,000 ft both manuals call for the same 4% reduction per 1,000 ft, so neither has an advantage in the high desert.
With nothing overhead, debris is part of the picture. The Lanai's framed screen keeps sticks and leaves out of the firebox when the unit isn't in use. The manual describes it that way, not as a spark guard. The Courtyard owner's manual lists mesh screens as standard, and the unit's rating label calls for the ODCOUG-36SCN or 42SCN barrier; ask us to confirm what ships with yours. For monsoon storms, both units have drain holes in the base and need the 1/4" per foot slope toward the drain ports.
A covered porch
A porch with a roof and no more than two side walls counts as outdoors under both manuals. Close in a third wall and the 30% rule applies. The Courtyard manual gives a figure written for this setting: 36" clearance under a veranda, porch, deck or balcony. Both units can sit on a continuous flat wood, composite or noncombustible surface covering their full width and depth. Weight is worth checking on a raised wood porch, though: a Courtyard -NR weighs 90–95 lb, while a Lanai weighs 215–245 lb before any surround is built around it.
If you were thinking about an indoor fireplace for the porch, our indoor vs outdoor-listed fireplace guide explains why only outdoor-listed units like these two can go there.
The Courtyard needs a liner: choose it when you order
The Courtyard models we sell are the -NR versions, and the installation manual says they "MUST be finished with one of the available refractory kit options." Majestic adds that running the fireplace without one is an aesthetic issue only. Even so, it is the liner that gives the Courtyard its traditional look, so budget for one from the start. There are six brick-pattern refractory panel finishes (brown, black or gray, each in herringbone or traditional) and a stainless steel liner, available as Courtyard 36" liner panels or Courtyard 42" liner panels. For logs, Majestic lists standard and high-definition log sets for the Courtyard, used with its stainless grate. They aren't listed online, so ask us about availability.
The Lanai has no liner. You choose between the Contemporary Driftwood Log Set (CDLS) and the Stone Kit. The owner's manual says the two can't be used together.
Propane, drain pans and power
Our Lanai listings ship set up for natural gas. For propane, add the LPK-ODLANAIG48 or LPK-ODLANAIG60 kit. The Courtyard converts with ODCOUG-LPK. We don't list that kit online yet, so ask us about availability. Drain pans for either unit aren't listed online either. Ask us about those too. Have your electrician run an unswitched, GFCI-protected 110–120V circuit to the fireplace location before the finish goes on. Both units need one.
The warranty doesn't tip the decision either way, because both carry the same Outdoor Lifestyles Limited Warranty. Its exclusions include prolonged dampness, condensation, ice or snow, water or weather damage, and atmospheres contaminated by chlorine. That's one more reason to plan drainage before you build. For more on the wider product range, see our Majestic fireplaces buyer's guide.
REMEMBER
Your local authority having jurisdiction may enforce building codes that differ from the manufacturer's instructions. Outdoor gas fireplaces must be installed by a qualified, licensed installer, following the appliance's installation manual for gas supply, electrical, clearances to combustibles and the enclosure.
Send us photos of your patio, lanai or porch and the measurements (ceiling height, wall lengths and which sides are open or screened), and we'll tell you which unit and size fits before you order.
By Matthew Murphy